Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Specifying the wrong cable size is one of those mistakes that costs you on the return visit. This guide covers the most common domestic cable sizes — 1mm, 1.5mm, 2.5mm and 4mm Twin & Earth — and when each one is correct.
Cable sizes refer to the cross-sectional area (CSA) of each conductor in square millimetres (mm²). A 2.5mm² cable has conductors with a cross-section of 2.5mm². Larger CSA = lower resistance = more current-carrying capacity.
Twin & Earth (T&E) cable — the standard for most UK domestic fixed wiring — has two insulated conductors (live and neutral) plus an uninsulated earth. It's specified for mains voltage (230V) circuits.
Current rating (clipped direct): 15A
Used for lighting circuits. A standard domestic lighting circuit typically runs at 6A with a 6A MCB — 1mm² is appropriate for this load. The most common use is the final ring or radial circuit for fixed lighting.
Also used for low-load signal circuits (doorbell transformers, some thermostat wiring) though purpose-made signal cable is sometimes more appropriate.
Don't use 1mm² for: Socket circuits, shower circuits, hob circuits, or any high-load application.
Current rating (clipped direct): 20A
Lighting circuits where runs are long and you want the extra headroom, or higher-load lighting (LED drivers, fluorescent luminaires). Some electricians default to 1.5mm² for all lighting as a belt-and-braces approach.
Also used for dedicated appliance spurs where the load is under 20A — fridge, freezer, some washing machines where a dedicated circuit is preferred over the ring.
Current rating (clipped direct): 27A
The most-used domestic cable size. Protected by a 20A MCB on ring final circuits (the ring effectively halves the load) and used for:
If you're doing a rewire or extension and one cable size will go on the van for most jobs, 2.5mm² T&E is it. We cut it from the drum — any length, no minimum, no overbuying a 100m coil for a 12-metre circuit.
Current rating (clipped direct): 37A
Higher-load dedicated circuits:
For a 9.5kW shower: 9500W ÷ 230V = 41.3A. You need a 45A MCB and 6mm² cable — 4mm² isn't sufficient for this specific case. Always calculate actual load before specifying.
For high-load circuits — large showers, EV chargers, cookers, outbuilding feeds. See the wider electrical range for related accessories. Beyond the scope of this guide, but we stock it. Call us to confirm availability on specific sizes.
The current ratings above assume cable clipped direct to a surface in open air (Installation Method C). If your cable is:
Always refer to BS 7671 Appendix 4 for the correct current-carrying capacity for your installation method. The above figures are a starting guide, not a substitute for a proper calculation.
| Size | Typical use | MCB rating |
|---|---|---|
| 1mm² | Lighting circuits | 6A |
| 1.5mm² | Lighting, low-load spurs | 10A |
| 2.5mm² | Ring finals, appliance circuits | 20A (ring) / 20A (radial) |
| 4mm² | Showers, hobs, EV spurs | 32A–40A (load dependent) |
| 6mm²+ | High-load dedicated circuits | 40A+ (calculate) |
We cut Twin & Earth cable from the drum. Need 8 metres of 2.5mm² for a kitchen circuit extension? Pay for 8 metres. No 50m minimum, no leftover coil in the van.
This is an in-store service only — available at our Acton trade counter, Mon–Sat. Contact APM to confirm the size you need before visiting.
APM Plumbing & Electrical Supplies
24 Western Avenue, Acton, London W3 7TZ
📞 020 8702 8080 | 🌐 apmi.uk
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment