Every sealed heating system needs a way to fill, bleed air, and drain when service or repair is required. Drain valves, air vents, and automatic air eliminators are among the least glamorous products in a plumber's van, but specifying or fitting the wrong one causes problems long after the job is signed off — a corroded drain cock seizing during a future flush, an automatic air vent weeping onto a boiler casing, or persistent air locks in a system that should vent itself. This guide covers the product types, standards, installation requirements, and the situations where each applies.
Drain cocks (also called drain valves or draining cocks) in heating systems are specified under BS 2879:1980 — the British Standard for draining taps. The standard defines three types:
For central heating systems, Type C hose union drain cocks are the correct specification for service drain points. Type B key-operated drain cocks are appropriate for auxiliary drain points on radiator tails or low points in pipework runs.
Every section of pipework that could trap water and prevent complete draining must have a drain point at its lowest accessible position. Key locations include:
In practice, most domestic boiler installations provide a single drain cock at the lowest point of the primary circuit — typically a 15mm or 22mm hose union fitted in the flow or return immediately at the boiler. Ensure the drain cock is accessible without removing the boiler casing and that a drain hose can reach a suitable drain point or bucket position.
Drain cocks for heating systems are most commonly specified in:
Standard drain cock sizes:
Where individual radiators need to be isolated for removal without draining the system, a combination of isolating valve (or TRV with lockshield) and radiator bleed valve is sufficient. For radiators in exposed or frost-risk positions, a drain cock can be fitted to the lower tapping in lieu of a blanking plug. This allows the radiator to be drained without affecting the remainder of the circuit.
The most common manual air vent in domestic heating is the radiator bleed valve — a simple 1/8" BSP plug with a slotted or square key-operated bleed screw. When air is trapped in the top of a radiator body, the bleed valve is opened with a radiator key (available in brass or plastic) until water runs from the bleed point, indicating the air has been displaced.
Bleed valves are non-repairable consumables — when the internal packing fails, replace the entire valve assembly. Most radiators use a standard 1/8" BSP thread; replacement valves are interchangeable between brands. Some modern designer radiators use a hex key socket in lieu of a square key pattern.
The correct procedure for bleeding a sealed system radiator:
Air can also be trapped in pipework high points — particularly in microbore systems, horizontal runs with inadequate flow velocity to carry air through, and in systems where the pump has been oversized or sited incorrectly. Manual air vents for pipework (as opposed to radiators) are screwed into 1/8" or 1/4" BSP bosses welded or tapped into the pipe at the high point.
Lever-key air vents (using a standard radiator key or flat-blade screwdriver) are the common specification. They are available in:
Automatic air vents (AAVs) remove air from heating systems without manual intervention. A float mechanism inside the body rises and falls with water level: when air collects inside the chamber, the float falls, opening a needle valve that releases air to atmosphere. When water fills the chamber, the float rises and closes the valve.
Standard AAVs are available in two configurations:
A lockshield cap is supplied with most AAVs. The cap closes the valve outlet and is used during system filling to prevent the float chamber from becoming contaminated with flux, solder debris, or inhibitor before the circuit is clean. Once the system is filled and circulating, remove the cap to allow normal venting operation.
Standard float-type AAVs remove free air — large air bubbles that collect in the chamber. They are less effective at removing dissolved air (micro-bubbles that are carried throughout the system by the circulating water). Dissolved air causes noise (kettling, gurgling), accelerates corrosion, and contributes to magnetite formation.
Micro-bubble air eliminators (also called deaerators or combined air and dirt separators) address this by:
Combined air and dirt separators (Flamcovent, Spirovent, Caleffi 546/547 series, Fernox Omega) are now considered best practice on primary circuits, particularly where magnetic filters are not separately installed. They mount inline on the flow pipe, close to the boiler or heat pump. Sizes: 22mm–54mm compression or end-feed connections, or flanged versions for commercial plant.
AAVs should be positioned at circuit high points — typically the top of a vertical flow from the boiler, or at the highest point in each zone circuit. Key positioning rules:
The most frequent AAV failure is a weeping needle valve — the valve does not fully seat due to debris on the seat face. Symptoms include a constant drip from the cap area or salt deposits on the body indicating long-term slow leakage. Corrective action:
A second failure mode is a seized float — the float corrodes or deposits cause it to stick in the open or closed position. A stuck-open float results in water loss; a stuck-closed float means air is not vented. Test by shaking the body (off-system) — the float should move freely.
Combined filling/draining units (Altecnic Combiflex, JG Speedfit Fill Point) integrate a fill valve, system pressure gauge, drain cock, and sometimes a dirt trap in a single assembly. They are commonly fitted on the return pipework near the boiler, providing a single service point for:
Pressure test points (also called Schrader test nipples) are small push-fit blanked valves inserted at circuit monitoring positions. A push-on pressure gauge (Magnehelic, Comark, or system gauge) can be connected and disconnected without draining. These are useful for setting differential pressure across zone circuits or for commissioning pump head calculations.
Heating system inhibitors (Fernox F1, Sentinel X100, Adey MC1+) should be introduced into the sealed system via a dedicated dosing point — not via the filling loop, which introduces diluted inhibitor mixed with mains water. Most fill/drain assemblies include an inline port for a dosing bottle. Alternatively, a radiator can be partially drained and the inhibitor bottle connected to the bleed valve using a proprietary adapter. Following BS 7593:2019 (code of practice for water treatment of heating systems), inhibitor should be dosed at first fill and checked annually during boiler service.
Under the Domestic Building Services Compliance Guide (which supports Part L of the Building Regulations), a new boiler or central heating system must be commissioned using a recognised methodology — typically the HHIC / HPA checklist or the boiler manufacturer's own commissioning procedure. The commissioning record must include confirmation that the system has been:
This commissioning data is required for CORGI-Gas (now Gas Safe) registration, HIES warranty compliance, and manufacturer warranty purposes. An air vent or drain cock that is inaccessible — buried in a floor screed, hidden behind fixed cabinetry, or inside a sealed unit without an access panel — will prevent this commissioning from being properly completed and may void the boiler warranty.
Drain valves, air vents, and air eliminators are not afterthoughts — they are part of a properly designed and commissioned heating system. Fitting a hose union drain cock at every serviceable low point, an automatic air vent at every permanent high point, and a combined air/dirt separator on the primary flow circuit gives the next engineer attending the system the access and information needed to service it correctly. Getting these basics right reduces callbacks, facilitates future powerflushes and repairs, and satisfies BS 7593 and Part L commissioning requirements without additional effort.
Related guides: expansion vessels, sealed system pressure and filling loops, heating inhibitor and system flushing, central heating pumps, powerflush, radiator balancing, thermostatic radiator valves, magnetic filters.