Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Boiler controls govern when a heating system fires, for how long, and to what temperature. Getting control specification right determines both Part L compliance and whether the customer actually stays comfortable and saves money on bills. This guide covers the four main control types — boiler programmers, room thermostats, cylinder thermostats, and thermostatic radiator valves (TRVs) — and how they work together as a system under current Building Regulations requirements.
Since April 2018, new gas boiler installations in England must comply with the Boiler Plus standard, which sits within Part L of the Building Regulations. The key requirements are:
In Scotland and Wales, similar requirements apply under respective Technical Standards. For like-for-like boiler replacements in existing systems, upgrading controls to meet these requirements is strongly recommended and often required under the competent person scheme notifications.
A programmer allows the user to set when the central heating and (on S-plan or Y-plan systems) hot water circuits are active. It does not control temperature — it only governs the time periods the system is permitted to fire.
Types of programmer:
Wiring connections: Programmers use switched Live outputs to call for heating (CH) and hot water (HW) — these switch the relevant motorised zone valve (S-plan) or the mid-position valve (Y-plan). On a combi boiler without a hot water cylinder, the HW output is not used; the programmer only needs to switch the CH circuit.
Most programmers use standard 2-gang wiring (Danfoss, Drayton, Honeywell/Resideo) with a compatible back-plate — check the back-plate compatibility before ordering a replacement.
A room thermostat senses air temperature in the main living area (typically the lounge or hallway) and sends a call for heat to the boiler when the temperature drops below the set point. It is the primary temperature control device for the heating circuit.
Where to position:
The radiator in the thermostat room must not have a TRV (or must have a locked-open TRV) — this ensures the thermostat always has a demand signal. If every radiator had a TRV that could close, the boiler would have no heat emitter to satisfy and would short-cycle continuously.
Wiring: Room thermostats are wired as volt-free switches in the Live call-for-heat circuit. Most operate at mains voltage (230V) — they are not low-voltage devices and must be installed by a competent person. Some (particularly wireless/smart thermostats) are battery-powered heads connected to a wired receiver.
Types:
A cylinder thermostat is used on systems with a hot water storage cylinder (open-vented or unvented). It is strapped to the outside of the cylinder and senses water temperature. When the temperature drops below the set point, it sends a call for heat to the hot water circuit.
Standard setting: 60°C. This is the minimum temperature recommended by the Health and Safety Executive and ACOP L8 (Legionella control) for stored hot water — at 60°C, Legionella bacteria die within a few minutes. Setting below 60°C saves energy but creates a Legionella risk, particularly in rental properties and communal systems. Setting above 65°C increases scalding risk.
Positioning: The cylinder thermostat should be positioned approximately one-third up from the bottom of the cylinder — this ensures the lower portion (which is heated first by the coil) is being read, not just the top hot layer.
Cylinder thermostats must be used in conjunction with a motorised valve — the thermostat alone does not fire the boiler; it opens the valve, which then energises the boiler via the pump relay in the programmer or wiring centre.
Boiler interlock is not a physical device — it is a wiring configuration that prevents the boiler firing when there is no demand from the thermostat. On a correctly interlocked system:
A system without interlock allows the boiler to run on its own thermostat even when the house is warm — this is inefficient and non-compliant. Signs of a non-interlocked system: the boiler fires at times when no heating or hot water has been requested; the radiators are warm when the programmer is set to "off".
Y-plan (mid-position valve): Uses a single 3-port motorised valve (mid-position). The valve has three positions: fully heating, fully hot water, or mid-position (both). Used with a 5-wire wiring centre. Older scheme, still widely found in existing UK systems. The mid-position valve is a wearing component — it fails more often than a simple 2-port valve.
S-plan (2-port zone valves): Uses two separate 2-port motorised valves — one for heating, one for hot water. Each circuit is independently controlled. More reliable, easier to diagnose, and the heating can run while hot water is being heated. Recommended for new installations. Easy to extend to an S-plan plus (3 zones or more) by adding additional valves and a third thermostat.
APM stocks a full range of boiler and heating controls for new installations and like-for-like replacements: 7-day and 5/2 programmers (Honeywell Resideo, Drayton), digital programmable room thermostats, analogue room thermostats, and cylinder thermostats with standard 1.5m lead. We also carry 2-port and 3-port motorised valves for S-plan and Y-plan systems, and Heatmiser and Drayton Wiser smart thermostats for Boiler Plus upgrades.
Browse our heating controls range or visit the Acton trade counter. Trade orders placed before 2pm ship same day across London and the South East.
Key heating programmers and thermostats available for trade collection or delivery:
APM Electricals, 24 Western Avenue, Acton, London W3 7TZ. Call 020 8702 8080 or visit www.apmi.uk for same-day trade counter collection and next-day delivery across London and the UK.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment