Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
A heating system bypass is one of those components that installers sometimes overlook until a pump fails prematurely or a boiler throws a fault. Understanding when a bypass is required, what type to fit, and how to set it correctly is essential knowledge for any heating engineer working on wet central heating systems in the UK.
This guide covers the purpose of system bypasses, automatic bypass valve (ABV) selection and sizing, pump overrun requirements for condensing boilers, and the common installation errors that lead to noisy systems and early pump failure.
When thermostatic radiator valves (TRVs) close — either because room temperatures have been reached or during setback periods — the circulating pump still runs. If all TRVs close simultaneously, the pump has nowhere to push water and pressure builds rapidly in the circuit. Without a bypass, this creates:
A bypass provides a permanent minimum flow path so that the pump always has somewhere to circulate water, regardless of TRV position.
BS EN 12828 and boiler manufacturers' technical data sheets both define minimum flow rates for safe operation. As a general rule:
Exception: A system where at least one radiator remains permanently open (e.g., one radiator without a TRV, acting as the "open radiator") does not require a separate bypass, provided the permanently open circuit provides adequate minimum flow. However, all-TRV systems are now standard under current Building Regulations, so an external bypass is almost always required.
A fixed bypass is a permanently cracked-open lockshield valve or a fixed-diameter orifice fitted between the flow and return pipes. It provides a constant bleed path regardless of system conditions.
Advantages: Simple, no moving parts, very low cost
Disadvantages: Wastes energy — even when TRVs are open and the full system is circulating, the bypass bleeds warm water from flow to return, reducing efficiency. Not recommended for new installations under Part L.
An ABV opens proportionally in response to differential pressure across the valve. When TRVs are open and the pump is circulating freely, the differential pressure is low and the ABV remains closed. As TRVs close and the pressure differential rises, the ABV opens to provide the minimum flow path.
Advantages: Energy-efficient, self-regulating, SEDBUK/ErP compliant
Disadvantages: Slightly higher cost than a fixed bypass; requires correct setting
Automatic bypass valves are the recommended and most common solution for domestic heating systems. Brands commonly stocked include Honeywell Home (DU145), Altecnic, and Reliance Water Controls.
A DPBV is similar in principle to an ABV but is typically used in larger commercial or multi-zone systems where more precise control of differential pressure is needed. They are often sized to specific pump curves and are adjustable over a wider range than domestic ABVs.
Most domestic ABVs are adjustable between 0.1 and 0.6 bar differential pressure. The correct setting depends on the pump and boiler minimum flow requirement:
| System Type | Recommended Setting |
|---|---|
| Standard domestic radiator system, 3-speed pump | 0.2–0.3 bar |
| Combi boiler system with plate HX | 0.15–0.25 bar (check boiler data sheet) |
| Underfloor heating primary circuit | 0.1–0.2 bar |
| Larger domestic (10+ radiators) | 0.3–0.5 bar |
Rule of thumb: Set the ABV to open at approximately 0.2–0.3 bar above the pump's closed-head pressure. For most domestic Grundfos UPS2 or Wilo Para pumps, this is in the 0.2–0.35 bar range.
The ABV should be fitted:
Common error: fitting the ABV on the primary side of zone valves in an S-plan or Y-plan system. In this position the bypass is useless — when a zone valve closes, the bypass sees no differential pressure from that zone and remains shut. The ABV must be on the secondary (radiator circuit) side of each zone valve, or one per zone.
Modern condensing boilers require the circulating pump to continue running for a period after the boiler burner shuts off. This is called pump overrun. Its purpose is to:
Pump overrun times typically range from 2 to 5 minutes depending on boiler output and type. Check the boiler's installation and commissioning manual for the specified overrun period.
In modern systems, pump overrun is handled in one of two ways:
A frequent commissioning mistake is wiring the circulating pump directly to the programmer/room thermostat switching live rather than to the boiler's pump output. This means the pump stops the moment the heating demand drops — before the boiler has cooled. Over time this causes:
Always wire the pump to the boiler's internal pump terminal or use an external pump overrun thermostat on legacy systems.
In S-plan and Y-plan zoned heating systems, the interaction between zone valves, the pump, and the bypass becomes more complex:
A Y-plan system uses a mid-position zone valve with three ports: heating, hot water, and mid-position (both). When only the hot water zone is calling, the heating circuit is closed. The pump continues to run — meaning the ABV on the heating circuit must be functional, or the pump cavitates against the closed valve. One ABV on the heating circuit (secondary side) is sufficient.
An S-plan system has separate zone valves for heating and hot water. When neither zone is calling but the pump overrun period is active, both zone valves are closed. In this case, the ABV must be on the primary circuit upstream of both zone valves — or, better, fit one ABV per zone circuit. Consulting the wiring centre manufacturer's schematic is essential for correct placement.
Diagnosis: ABV set too high or not opening — differential pressure exceeds pump operating point. Check ABV setting and reduce by 0.05–0.1 bar increments. Verify ABV is opening by feeling the bypass pipe — it should warm up when TRVs are closed.
Diagnosis: ABV set too low — bypass is open even with TRVs open, mixing hot flow with cold return. Increase setting by 0.05–0.1 bar. Alternatively, check for a stuck-open ABV (corroded or debris-fouled).
Diagnosis: High differential pressure across TRVs — often caused by a poorly set or absent bypass, or by a pump running on too high a speed. Reduce pump speed setting first; if chattering persists, check and set ABV.
Diagnosis: Insufficient flow through heat exchanger. Check ABV is present and operative. Check that zone valves have not all closed simultaneously. On combi boilers, confirm minimum flow rate is within boiler specification.
Wet underfloor heating systems operate at low flow temperatures (typically 35–45°C for screed systems, 45–55°C for suspended timber) and use manifolds with individual loop actuators. When all actuators close, the manifold pump is at risk in the same way as a radiator circuit with all TRVs closed.
UFH manifolds typically incorporate a differential pressure bypass valve integrated into the manifold assembly, or a separate bypass connecting the flow and return rails. This is often factory-set; check the manifold data sheet for the correct bypass setting.
UFH mixing valves (which reduce primary flow temperature to UFH circuit temperature) also need careful bypass design — too little flow through the mixing valve causes temperature hunting. Follow the mixing valve manufacturer's minimum flow guidance.
APM Electricals stocks a full range of central heating bypass valves and heating components for trade professionals. Same-day collection from our Acton trade counter.
Browse our full Heating & Controls range at apmi.uk. Visit us at 24 Western Avenue, Acton, London W3 7TZ or call 020 8702 8080.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment