Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Electric storage heaters remain one of the UK's most common heating systems — accounting for around 8% of homes and a much higher proportion in flats, social housing, and all-electric properties without gas supply. For electricians, they represent a steady workload: new installations in properties coming off night-rate tariffs, replacements driven by the Lot 20 regulation, and fault diagnosis on ageing units.
This guide covers how storage heaters work, the Lot 20 requirements that changed the market from 2018, wiring and installation under BS 7671, Economy 7 tariff considerations, and troubleshooting common faults.
Storage heaters charge up overnight using cheaper off-peak electricity — typically Economy 7 or Economy 10 tariffs — and release that stored heat during the day. Internally, they contain high-density ceramic bricks (usually aluminium oxide or magnetite) that can absorb and retain large amounts of heat energy.
The basic operating cycle:
Manual storage heaters (legacy)
The simplest type: an input dial controls how much electricity the heater charges overnight, and an output control (a damper or damper rod) regulates how fast heat is released during the day. No electronic controls, no thermostat. These are the old-style units found in properties built pre-2000. Still functional if the elements and bricks are intact, but no longer compliant for new installations under Lot 20 and often inefficient due to heat loss through basic insulation.
Automatic or electronic storage heaters (transitional)
Introduced from the 1990s onwards. An electronic thermostat or room temperature sensor controls the charging level automatically, adjusting input based on ambient temperature and user set-point. Output is still manual in basic versions. More efficient than purely manual units.
High heat retention storage heaters (HHRS) — Lot 20 compliant
The current standard. Required for all new installations (and replacements of existing heaters) since January 2018 under the Lot 20 Ecodesign regulation. These heaters use superior insulation to reduce standby heat loss to less than 1.5% of stored energy per hour (compared to 5–10% in older units). They incorporate:
Manufacturers offering Lot 20 compliant heaters include Elnur, Dimplex, Creda, and Haverland. Capacity is measured in kWh (storage capacity) rather than kW output rating. Common sizes are 1.0 kWh to 3.0 kWh storage capacity.
Lot 20 refers to Commission Regulation (EU) No 813/2013 (space heaters) and Commission Regulation (EU) No 814/2013 (water heaters), transposed into UK law as retained EU legislation. The space heater provisions relevant to storage heaters came into force in January 2018.
Old manual storage heaters — even if still working — cannot be replaced on a like-for-like basis with equivalent manual units. Any new or replacement heater must be a Lot 20-compliant HHRS. Practically, this means:
There is no enforcement mechanism for legacy units already installed and operating, but any notifiable electrical work (which replacement of a storage heater may be, if a new circuit is required — see Part P below) will be inspected under current regulations.
Storage heaters are designed to exploit off-peak electricity tariffs, where the cost per kWh is significantly lower during overnight hours.
The standard off-peak tariff. Provides 7 hours of cheaper electricity, typically from around 00:30 to 07:30 (exact times vary by DNO region and supplier). The off-peak rate is usually 30–50% lower than the daytime rate, though the daytime rate on Economy 7 is typically higher than a standard single-rate tariff — making Economy 7 only cost-effective if at least 40–45% of electricity consumption is during off-peak hours.
Provides 10 hours of cheaper electricity, typically split across two or three overnight/afternoon windows. More flexible for households that use more electricity in the afternoon. Less widely available than Economy 7.
Smart meters have enabled dynamic time-of-use tariffs (such as Octopus Agile or Go) with variable pricing. Lot 20-compliant HHRS with smart controls or OpenTherm/Zigbee connectivity can be programmed to charge during the cheapest overnight windows, potentially reducing running costs further. This is an emerging area relevant to installers working in all-electric new-build properties.
Economy 7 properties have a two-rate meter (or a smart meter programmed for two rates) and typically a separate consumer unit or timeswitch that controls the off-peak circuit. The off-peak circuit feeds storage heaters, immersion heaters, and sometimes a hot water cylinder. The switching may be done by:
Always verify the off-peak switching is working correctly before commissioning a new storage heater.
Storage heaters are high-wattage fixed appliances. Each heater must be on a dedicated radial circuit — they must not be connected to ring final circuits. The circuit must be sized to the heater's charge rating, not its output rating.
Typical charge ratings for Lot 20 HHRS:
Refer to manufacturer data sheets for exact charge element ratings and verify cable sizing against BS 7671 Appendix 4, accounting for installation method, grouping, and ambient temperature correction factors (see Cable Sizing and Current Carrying Capacity).
Storage heaters fed from an off-peak circuit require their own protection in the consumer unit. The off-peak consumer unit (sometimes called the night storage heater board) is typically separate from the main consumer unit and controlled by the meter timeswitch or ripple control. Each heater circuit must have:
Standard twin-and-earth cable (flat grey or white, typically 2.5mm²) is the norm for storage heater circuits. The cable run from the consumer unit to each heater position must be:
Terminations at the heater end use the heater's terminal block. Most modern HHRS units have a cable entry point at the bottom and require the cable to enter from a patress box or surface conduit box mounted below the heater.
A local means of isolation is required. For storage heaters, a double pole isolator switch (fused or unfused, typically 20A DP) should be installed adjacent to or at the heater position. Some units have an integral isolating switch. The isolator must be accessible without moving the heater.
Storage heaters must be earthed. The heater casing connects to the circuit protective conductor (CPC) of the supply cable. Where the heater is in a bathroom or kitchen, check whether supplementary equipotential bonding is required (see BS 7671 Section 701 for bathrooms — storage heaters are unusual in bathrooms but not unheard of in older properties). Main protective bonding requirements apply as normal (see Earth Bonding Guide).
Replacement of a storage heater on an existing circuit (same cable, same MCB) is not notifiable under Part P of the Building Regulations — it is classed as like-for-like replacement of a fixed appliance. However, if the work involves:
...then the work is notifiable and must be carried out by a competent person registered with an approved Part P scheme (NICEIC, NAPIT, ELECSA) or notified to the local authority building control (LABC). Always obtain a Minor Electrical Installation Works Certificate (MEIWC) or an Electrical Installation Certificate (EIC) as appropriate and issue it to the customer.
Where multiple heaters are being installed (typically in a flat or house conversion), plan the circuit layout to minimise cable runs. Label each circuit clearly in the consumer unit. A floor plan with heater positions and circuit numbers will be useful when commissioning and for the landlord's records.
A common rule of thumb for storage heater sizing is to use the property's calculated heat loss, then size the heater storage capacity to cover 8–10 hours of off-peak charging. As a guide:
This is approximate — actual sizing should account for insulation quality (cavity wall, loft insulation), glazing, ceiling height, and orientation. For larger projects (HMOs, blocks of flats, housing association properties), carry out a proper heat loss calculation using SAP methodology or BS EN 12831.
For supplementary heating in rooms where storage heater output is insufficient in late afternoon, a panel heater or convector heater on the peak-rate supply can be added — but advise customers that peak-rate electricity is expensive and this should be a last resort.
| System | Best For | Running Cost | Installation |
|---|---|---|---|
| Storage heater (HHRS) | Economy 7 properties, no gas supply, flats | Lowest on E7 tariff | Dedicated circuit, Part P if new circuit |
| Panel heater / convector | Supplementary heating, occasional use rooms | High (peak rate) | 13A socket or dedicated radial |
| Electric underfloor heating | Bathrooms, new builds, renovations | Medium (with programmer) | Dedicated circuit, zone controller (see Electric UFH Guide) |
| Air source heat pump | Whole-property replacement for gas boiler | Lowest overall but high capital cost | Major project, Boiler Upgrade Scheme eligible (see ASHP Guide) |
| Infrared panels | Supplementary, low-ceiling rooms | Medium-high | Wall/ceiling mount, dedicated radial or 13A socket |
APM Electricals — Plumbing, Electrical & Heating Supplies
24 Western Avenue, Acton, W3 7TZ
📞 020 8702 8080
Browse our full product range at apmi.uk
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment