Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Circuit protection is one of the most critical elements of any electrical installation. The 18th Edition of BS 7671 has tightened requirements significantly — RCBOs are now standard on most circuits in new domestic consumer units, SPD (surge protection device) is required on most new installations, and the old split-load consumer unit with a single RCD covering half the circuits is effectively obsolete for new work. This guide covers the circuit protection devices in stock at APM: Axiom MCBs, RCDs, RCBOs, consumer units, and isolators, alongside CED HRS rewirable fuses for older installations.
| Device | Protects against | Trips on | Modules |
|---|---|---|---|
| MCB (Miniature Circuit Breaker) | Overcurrent and short circuit | Overload (thermal) or fault (magnetic) | 1 module SP |
| RCD (Residual Current Device) | Earth fault / electrocution risk | Residual current imbalance ≥30mA | 2 modules DP |
| RCBO (Residual Current Circuit Breaker with Overcurrent) | Both overcurrent AND earth fault | Either overload/fault OR residual current ≥30mA | 1 module SP |
Why RCBOs are now the default: Under 18th Edition, fitting individual RCBOs to each circuit means that an earth fault on a shower circuit only trips that one RCBO — not the entire upstairs ring, lighting, and everything else on that side of a split-load board. This is the required approach for most new domestic consumer unit installations. RCBOs also satisfy the SPD bonding requirements more cleanly than split-load arrangements.
All Axiom MCBs stocked at APM are Type B. The type refers to the magnetic (instantaneous) trip threshold:
All Axiom MCBs have 6kA breaking capacity — correct for domestic and light commercial installations where the prospective short-circuit current (PSCC) does not exceed 6kA. Check the PSCC at the distribution board before selecting MCBs; installations with high PSCC (close to the network supply point) may require 10kA devices.
Double-pole 30mA RCDs for use as main protection in split-load consumer units, or for general fault protection on a sub-board where individual RCBOs are not being used. A 30mA RCD provides the minimum protection level required by BS 7671 for socket circuits and bathroom circuits.
Note: RCDs are 2-module devices. Plan the busbar space in the consumer unit accordingly — a 40A RCD protecting 6 MCBs occupies 2 ways, leaving 6 ways for MCBs in an 8-way board.
Type A RCBOs detect both AC residual current and pulsating DC residual current. BS 7671 18th Edition Amendment 2 (effective from October 2022) requires Type A RCBOs on circuits that may carry DC-component leakage — this includes EV charging points, inverter-controlled appliances, LED drivers, and circuits with variable speed drives. Type A is now the practical default choice for new domestic consumer units.
Axiom mini RCBOs are 1-module (single pole) — each occupies only one way in the consumer unit, the same as an MCB. This allows a full 12-way consumer unit to be fitted with 12 individual RCBOs, giving independent fault protection on every circuit.
12 MCB ways. 100A DP main switch. White dual-RCD metal enclosure. BS EN 61439-3 compliant. Suitable for new domestic installations under BS 7671 18th Edition. Accepts Type B MCBs or Type A mini RCBOs — or a combination. The 18th Edition requires SPD on all new consumer unit installations; an SPD can be fitted to one way of this board. Note: MCBs and RCBOs are sold separately.
For 3-phase machinery disconnection in workshops and light industrial premises. BS EN 60947-3 compliant. The rotary handle locks in the OFF position for safe maintenance isolation (lockout/tagout).
Where a socket outlet needs integral RCD protection — for example a garage socket, garden socket, or bathroom shaver supply — an RCD socket provides 30mA protection within the socket faceplate without using a consumer unit way.
HRS (High Rupture Capacity/Semi-enclosed rewirable) fuses are still found in older consumer units installed before the widespread adoption of MCBs. They are not appropriate for new installations but are a common service call item — a blown rewirable fuse must be replaced with the correct rating and fuse wire, never a substitute current rating.
For any new consumer unit installation under BS 7671 18th Edition (including Amendment 2, 2022):
All Axiom circuit protection devices and CED HRS fuses are in stock at APM's Acton trade counter — available for same-day collection.
APM Plumbing & Electrical | 24 Western Avenue, Acton, London W3 7TZ | 020 8702 8080 | apmi.uk
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment