Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Pressure testing is the final verification step before any new or modified pipework is concealed or put into service. A correct pressure test proves that joints are sound, fittings are correctly assembled, and the system will contain working pressure without leaking. A missed pressure test — or a test carried out incorrectly — leaves leaks hidden behind walls, floors, and ceilings where they cause progressive structural damage before becoming apparent.
This guide covers pressure testing procedures for domestic water supply pipework, central heating systems, and gas installations, including the relevant standards, equipment required, and pass/fail criteria.
Pipework fails at joints, not in the middle of pipe runs. A push-fit fitting that was not fully inserted, a compression fitting overtightened until the olive deformed, a soldered joint with a small void, a pipe union that was cross-threaded — these defects are not visible externally. They may pass a visual inspection and even hold water briefly, but will weep or fail under working pressure sustained over time. The pressure test applies a controlled stress that exposes these defects before the work is covered.
Building Regulations Part L (energy efficiency) and Part G (hot water safety) both require that installations are commissioned and tested. For unvented hot water systems, BS 7671, and gas systems, testing is either a legal requirement or a mandatory condition of the relevant standard or competent person scheme.
BS EN 806-4 (Technical specifications for installations inside buildings conveying water for human consumption — Part 4: Installation) provides the testing methodology for domestic and commercial water supply installations. The procedure involves filling the system with water (not air — an air pressure test on water supply pipework is potentially dangerous due to the stored energy in compressed air), applying test pressure, and observing for pressure drop.
For copper pipework systems at standard domestic working pressure (approximately 3 bar mains pressure), the test pressure is typically 1.5× working pressure — commonly set at 6 bar for a 4 bar system. For push-fit plastic pipework, manufacturers specify test pressures; JG Speedfit and Hep2O systems are typically tested at 1.5× working pressure (6–7.5 bar for standard domestic).
A sealed central heating system is filled via the filling loop until it reaches approximately 1.0–1.5 bar cold pressure (the exact target depends on the system volume and expansion vessel pre-charge — see the boiler or expansion vessel manual). After filling, the heating system is pressure tested before the boiler is fired.
Test procedure for a new sealed system:
Many manufacturers and industry guides specify 1.5× working pressure. For a system with a 3 bar safety relief valve (standard domestic), working pressure at full temperature is approximately 2.0–2.5 bar, so 1.5× = 3.0–3.75 bar — below the relief valve opening pressure. Some engineers test at 6 bar to give a more definitive test; the test pressure must always remain below the pressure relief valve setting to avoid spurious operation.
A small pressure drop over the observation period in a new system is normal — plastic and rubber components (O-rings, flexible hoses, expansion vessel membrane) compress slightly under pressure. After a 30-minute stabilisation, a correctly assembled system should show no further pressure drop over a subsequent 30-minute observation period. Any measurable ongoing drop after stabilisation indicates a leak.
Gas installations are tested under the Gas Safety (Installation and Use) Regulations 1998 and by reference to BS 6891 (Specification for the installation and maintenance of low pressure gas installation pipework). Gas pressure testing uses compressed air or nitrogen — never mains gas. Gas Safe registered engineers must carry out gas pipework installation and testing.
For domestic natural gas pipework at low pressure (up to 75 mbar):
For tightness testing of an existing installation (e.g. after appliance work), the procedure is simpler: apply working pressure via the gas meter (with all appliances isolated), observe the meter for movement over two minutes. For installations up to 25 m³/hr (most domestic premises), use a U-gauge or electronic manometer rather than the meter index, which lacks sufficient resolution.
The standard tool for gas soundness testing is an electronic manometer (e.g. Kane 3500, Testo 312-2) with resolution of 0.01 mbar and datalogging capability. Electronic manometers provide a definitive record of the test — essential for compliance and liability purposes. A purely visual observation of an analogue U-gauge is less reliable and does not produce a record.
Underfloor heating pipe (typically PE-Xa or PE-RT barrier pipe) is pressure tested before the screed is poured, as repairs afterwards require breaking up the floor. The pipe loops are pressurised and left under pressure during screeding to confirm integrity is maintained as the screed is poured over the pipes.
Procedure:
A pressure test result must be documented, particularly for:
The record should include: date and time, system or section tested, test pressure applied, duration, pressure at start and end of observation period, result (pass/fail), and engineer's name and registration number where applicable. Most electronic manometers can print or export a datalogged record — use this rather than a handwritten note where possible.
| Failure | Likely Cause | Investigation |
|---|---|---|
| Rapid initial pressure drop | Open valve or drain point; major leak at accessible joint | Inspect all connections; verify all valves closed |
| Slow ongoing pressure drop after stabilisation | Small leak at joint; push-fit not fully inserted; compression olive deformed | Check joints with leak detection fluid; use UV dye in heating systems |
| Pressure holds on water test but heating system pressurises overnight | Filling loop not closed after test; check valve leaking across filling loop | Inspect filling loop; replace if defective |
| Gas tightness test fails at meter end | Meter union or internal meter regulator weeping | Contact gas network distributor — do not attempt meter repairs |
| UFH pressure drops during screeding | Pipe kinked or damaged during pour; connection at manifold disturbed | Re-test loops individually to isolate failed loop; do not continue pour until resolved |
Pressure testing is not an optional extra — it is the minimum due diligence for any pipework installation. Use the correct procedure for each system type: hydraulic water test for water supply and heating (never air pressure test on water supply); compressed air or nitrogen for gas (never mains gas); sustained test pressure held throughout screeding for UFH. Document every test. A two-hour pressure test before closing up is infinitely less disruptive than a leak discovered six months later behind a tiled shower enclosure or under a finished floor.
At APM Plumbing & Electrical we stock plumbing tools and compression fittings for UK trade professionals.
Key pressure reduction valves and test equipment available for trade collection or delivery:
APM Electricals, 24 Western Avenue, Acton, London W3 7TZ. Call 020 8702 8080 or visit www.apmi.uk for same-day trade counter collection and next-day delivery across London and the UK.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment