Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Residual current devices (RCDs) are the front line of shock protection in UK electrical installations. The 18th Edition of BS 7671 — along with Amendment 2 (2022) — has significantly expanded the requirement for RCD protection, making it essential for electricians to understand the full range of device types, their applications, and how to test them correctly on site.
This guide covers RCCBs, RCBOs, SRCD sockets, combined arc fault detection, and how to specify the right device for each circuit type under current UK regulations.
An RCD monitors the current flowing out through the live conductor and returning through the neutral. Under normal conditions, these currents are equal. If current leaks to earth — through a person receiving a shock, a wiring fault, or a deteriorated appliance — there is a measurable imbalance. When that imbalance exceeds the device's rated sensitivity (typically 30mA for general protection), the RCD trips within milliseconds.
At 30mA the trip time must not exceed 40ms — well within the threshold at which ventricular fibrillation becomes likely. This is why 30mA protection is accepted as the standard for shock risk reduction, while 100mA or 300mA devices are used for fire protection only and must not be relied upon to protect persons.
An RCCB (sometimes referred to simply as an RCD) provides residual current protection only — it does not incorporate an overcurrent protective function. RCCBs are used in conjunction with MCBs, which provide overload and short-circuit protection upstream or downstream.
In a typical split-load consumer unit, an RCCB covers one group of MCBs — for example, all ring final circuits or all lighting circuits. A single 63A or 80A RCCB feeding multiple MCBs is cost-effective but has a drawback: if any circuit on the group has a fault, the entire RCCB trips, taking out all circuits on that side of the board.
RCCBs are available in 2-pole (single-phase, live and neutral switched) and 4-pole (three-phase, all four conductors switched) configurations. On domestic split-load boards, 2-pole RCCBs are standard. In commercial and industrial three-phase installations, 4-pole RCCBs protect groups of circuits from a 400V three-phase supply.
Current ratings for RCCBs in domestic installations are typically 40A, 63A, or 80A. The rating must be at least equal to the maximum demand of all circuits it protects simultaneously.
An RCBO combines the functions of an MCB and an RCD in a single 17.5mm or 18mm module. Each circuit has its own independent RCD protection: if one circuit trips on a residual fault, no other circuit is affected.
This selectivity makes RCBOs the preferred choice for modern consumer unit designs. Under the 18th Edition and Amendment 2, many electricians now fit all-RCBO boards, providing both circuit-selective tripping and full RCD protection on every final circuit — including those that previously relied on the main switch or upstream RCCB.
RCBOs are available in Type B, C, and D trip characteristics to match inductive loads, motor starting currents, and high-inrush equipment. The common ratings are 6A, 10A, 16A, 20A, 32A, and 40A, with 30mA sensitivity for general circuits. Dual-function RCBOs (Type B+D, or combined AFDD+RCBO in a single module) are also available for high-specification installations.
Socket outlets with integral RCD protection — commonly known as SRCD or RCD sockets — provide point-of-use protection at the outlet itself. They are commonly used to retrofit protection where an upstream RCD or RCBO cannot easily be added, and are mandatory in certain locations under BS 7671.
SRCD outlets are available as single or double gang, in white, brushed chrome, and other finishes. Always check that the socket is RoHS compliant and carries a BS 1363 approval mark. SRCD sockets have a test button and a reset button on the face and should be tested periodically using the integral test function.
PRCDs are plug-in RCDs used with portable equipment — particularly power tools on construction sites, agricultural settings, and outdoor locations. They are not a substitute for fixed RCD protection in the consumer unit, but provide additional protection where portable equipment may be used beyond the protection zone of the main installation.
Site PRCDs must be rated at 30mA and tested before use each working day. They should carry the CE mark and be rated to the appropriate current for the load connected.
A critically important distinction — and one that is often overlooked — is the type of residual current waveform that an RCD can detect. BS EN 61008 and BS EN 61009 classify devices into types:
The 18th Edition requires that the type of RCD is selected to be appropriate for the waveform of residual current that may arise from the load. Fitting a Type AC RCBO to a circuit feeding a modern EV wallbox, for example, would fail to provide protection against the smooth DC residual current that the charger can produce. This is a common compliance failure that electricians should audit for during periodic inspection work.
Amendment 2 to the 18th Edition (effective from January 2022 for new designs) significantly expanded mandatory RCD protection. Key changes affecting domestic and commercial installations include:
Where surge protection devices are fitted (now mandatory in many new and replacement consumer unit installations — see our SPD and AFDD guide), the interaction with RCDs must be considered. SPDs can introduce a measured leakage current under normal operating conditions, particularly Type 2 devices with varistor-based clamping. This can cause nuisance tripping on sensitive 10mA RCDs. For most Type 2 SPDs, 30mA RCDs are unaffected, but check the manufacturer's data sheet for maximum leakage current before specifying.
The test button on an RCD simulates a residual current condition and should cause the device to trip immediately. This tests the mechanical operation of the device but not its calibrated trip time or trip current. Every RCD should be tested in this way quarterly or after any event that may have subjected the installation to abnormal conditions.
When testing on a split-load board, note that the test button trips the RCCB (or RCBO) and disconnects all circuits on that group. Always warn occupants and isolate sensitive equipment before testing.
During periodic inspection and testing (EICR), or as part of initial verification after installation, RCDs must be tested with a calibrated RCD tester. This confirms both the trip time and, for some testers, the trip current.
For a 30mA general-purpose RCD:
Record all RCD test results on the schedule of test results or periodic inspection report, including the measured trip time at each test level. See our article on electrical installation testing for the full range of initial verification measurements required under BS 7671.
Nuisance RCD tripping — where the device trips without an apparent fault — is one of the most common complaints from occupants of recently rewired properties. Understanding the causes allows the electrician to diagnose and resolve the issue systematically rather than simply resetting the device.
Common causes include:
Certain locations require enhanced RCD protection beyond the standard 30mA general circuits:
When designing a new consumer unit or replacing an existing board, selecting the RCD protection strategy is one of the most important decisions:
Option 1 — Split-load board with RCCBs: Lower device cost but poor selectivity. Any residual fault on the protected group trips all circuits on that RCCB. Best suited to straightforward domestic rewires where cost is the primary constraint and the number of circuits is modest.
Option 2 — All-RCBO board: Each circuit independently protected. A fault on the kitchen ring does not affect lighting or heating circuits. Higher device cost but significantly better selectivity and end-user experience. Now the standard for quality domestic installations and all commercial fit-outs.
Option 3 — Dual RCD with selective protection: Two RCCBs with time-delayed (S-type) discrimination upstream and instant-trip downstream. Less common in domestic work but used in medical and commercial locations where continuity of supply to critical circuits is essential.
For consumer unit selection, sizing, and MCB/RCBO specification, see our detailed guide to consumer units, MCBs, and RCBOs. For wiring methods and cable selection that inform the overcurrent protection rating needed, see our cable selection guide.
All consumer unit replacements in England are notifiable under Part P of the Building Regulations, regardless of whether the work is otherwise straightforward. Where the work is carried out by a registered competent person (NAPIT, NICEIC, ELECSA, or STROMA), it can be self-certified. Where carried out by an unregistered electrician, a Building Control notification must be submitted before work commences.
Evidence of RCD protection — including the schedule of test results showing RCD trip times — must be provided in the Electrical Installation Certificate (EIC) issued upon completion. Without this, the installation cannot be said to comply with BS 7671 or Part P. See our Part P guide for full details of notification requirements and the self-certification process.
APM Electricals stocks a range of RCBOs, RCCBs, and consumer unit accessories from leading brands. Our range includes Type B and Type C RCBOs in 30mA sensitivity for all standard domestic and commercial circuit types, compatible with major consumer unit ranges. Browse our RCBO range for current stock and pricing.
Visit us at APM Electricals, 24 Western Avenue, Acton, W3 7TZ. Call 020 8702 8080.
APM Electricals
24 Western Avenue, Acton, London W3 7TZ
Phone: 020 8702 8080
www.apmi.uk
Trade counter open Monday–Friday. Same-day collection available on stocked items.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment