Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Solar photovoltaic (PV) installation is one of the fastest-growing areas of domestic electrical work in the UK. With energy bills at record highs and the Smart Export Guarantee (SEG) paying customers for excess generation, demand from homeowners and landlords is strong. This guide covers everything a qualified electrician needs to know: system design, installation procedure, inverter selection, battery storage integration, G98/G99 DNO notification, and MCS certification requirements.
Solar panels generate direct current (DC) electricity when photons strike semiconductor cells — typically silicon. This DC output is converted to 230V 50Hz AC by an inverter, which synchronises with the grid and exports surplus generation or charges a battery storage system. UK residential systems typically range from 3.5kWp to 12kWp depending on roof space, orientation, and load profile.
Solar PV installation is notifiable under Part P of the Building Regulations in England and Wales. All electrical work must comply with BS 7671:2018 (18th Edition), specifically:
The array wiring (DC side) is typically 4mm² or 6mm² single-core DC PV cable (double-insulated, UV-resistant). Never use standard AC cable on the DC side — it is not rated for the continuous high DC voltages involved (open-circuit voltage on a 10-panel string can exceed 400V DC).
To qualify homeowners for the Smart Export Guarantee (SEG), the installation must be carried out by a MCS-certified installer using MCS-certified products. MCS (Microgeneration Certification Scheme) accreditation requires:
At completion, provide the homeowner with an MCS certificate, EPC (if applicable), and a Handover Pack including operating manuals and monitoring app setup.
Before connecting any generation plant to the grid, you must notify the Distribution Network Operator (DNO):
Most domestic systems (4–6kWp) on single-phase supplies require G99 approval. Submit the G99 application as early as possible in the project lifecycle. The DNO may require an export limiter or reduced export capacity.
A proper site survey must establish:
String design must keep the open-circuit voltage (Voc) within the inverter's maximum DC input voltage (typically 1000V DC for residential inverters) at the lowest expected temperature (-10°C in the UK). Use the panel manufacturer's temperature coefficient to calculate worst-case Voc. As a rule of thumb, limit UK residential strings to 8–12 panels per string on a 1000V inverter.
The string must also keep the inverter's MPPT range (typically 200–800V DC) during peak generation. Too few panels and the string will sit below the MPPT minimum; too many and you clip generation at high irradiance.
Most UK systems use aluminium rail mounting systems fixed through the roof covering into the rafters with stainless-steel hooks or brackets:
Run 4mm² or 6mm² DC PV cable from panels to the inverter location. Cables exit the roof through a purpose-made roof cable entry gland. On the roof, cable is clipped to the underside of the rail system. Protect against mechanical damage where cables pass through roof penetrations.
All DC cables must be clearly labelled with "DC PV Cable — DANGER: Live during daylight hours" at both ends and at intervals. Use MC4 connectors for panel-to-panel connections — crimp correctly (use the proper MC4 crimp tool) to prevent arc faults, which are a fire risk on DC circuits.
Install a DC isolator within 500mm of the inverter, accessible to the installer and emergency services. Some installers also fit a rooftop DC isolator to allow the string to be isolated at the array.
Inverters should be located in a cool, ventilated position — a garage or utility room is ideal. Avoid direct sunlight and locations above 40°C ambient. Wall-mount on a fire-resistant surface, leaving clearance as specified by the manufacturer for airflow.
Connect DC input from the array (observing polarity — DC reverse polarity will damage the inverter), and AC output to the consumer unit or dedicated AC combiner box. Fit surge protection device (SPD) on both DC and AC sides per BS 7671 Regulation 443.
The AC connection is typically a dedicated 20A or 32A circuit from the consumer unit using 2.5mm² or 4mm² twin-and-earth cable protected by an MCB of the correct rating. The generation meter is fitted in the AC line between the inverter and the consumer unit.
For a DNO-metered system, the generation meter is typically fitted between the inverter and consumer unit in a separate generation meter tails enclosure. Ensure the meter is accessible for reading.
Label the AC isolator, generation meter, and consumer unit MCB clearly: "SOLAR PV GENERATION — ISOLATE BEFORE WORKING ON MAINS". Fit a warning label at the consumer unit indicating PV generation is present.
The inverter chassis and metal mounting rails must be earthed. On TN-C-S (PME) supplies, check with the DNO before earthing the PV frame to the PME earth terminal — some DNOs prohibit this. Where prohibited, use a separate earth electrode for the PV frame.
The DC negative conductor must not be earthed (on transformerless inverters, the negative is floated at mid-potential to improve efficiency).
For most UK homes, 5–15kWh of usable battery capacity is typical. A 10kWh battery can shift most surplus daytime generation to evening use in summer, but will be exhausted by early morning in winter. Model expected self-consumption rates based on the household's evening load profile.
Batteries must be installed as per manufacturer instructions, BS EN 62619 (safety requirements for lithium-ion batteries), and the relevant product safety guidance. Key requirements:
Before energising:
Issue the completed test schedule (IEC 62446-1 commissioning report) along with the MCS certificate and handover pack.
The SEG replaced the Feed-in Tariff in January 2020. Energy suppliers with more than 150,000 customers must offer SEG payments. Rates vary — typically 3p–15p/kWh — and are set by individual suppliers. To register:
Advise customers to compare SEG rates before committing to a supplier. Octopus Energy and OVO typically offer competitive export rates.
Solar PV systems are generally low-maintenance, but annual checks are recommended:
Type 2 surge protection device rated to 100A, designed for DIN-rail installation at the consumer unit. Provides AC-side overvoltage protection as required by BS 7671 Regulation 443 for solar PV installations. Essential for both new-build and retrofit PV systems to protect inverter electronics and downstream circuits from transient spikes.
Single-module RCBO providing simultaneous overcurrent and 30mA RCD protection. Type A rating detects pulsating DC fault currents typical of inverter-connected circuits. Ideal as the dedicated MCB/RCD for the 20A AC inverter feed circuit at the consumer unit, eliminating the need for separate MCB and RCD devices.
20A double-pole isolator switch in a robust metal-clad enclosure, suitable for indoor or sheltered external locations. Used as the AC disconnect switch between the inverter and consumer unit, or as a DC array isolator at the inverter input. Must be positioned within 500mm of the inverter and clearly labelled per BS 7671 requirements.
Compact double-pole RCBO rated at 32A 30mA for applications where a larger inverter output or battery storage system requires a 32A dedicated circuit. Type A detects pulsating DC residual currents. Fits standard consumer unit busbars. Also suitable for AC-coupled battery inverter feeds requiring combined overcurrent and RCD protection.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment