Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
The consumer unit — commonly called a fuse board or distribution board — is the heart of any domestic or commercial electrical installation. It houses the main switch, overcurrent protection devices (MCBs or fuses), and residual current devices (RCDs or RCBOs) that protect individual circuits. Since BS 7671:2018 (the 18th Edition IET Wiring Regulations) and Amendment 2 (2022), the requirements for consumer unit design, RCD protection, and surge protection have significantly changed. This guide covers consumer unit types, circuit protection selection, the 18th Edition requirements, and practical installation guidance for qualified electricians.
The simplest type: a single main switch (100A double-pole) with individual MCBs. No RCD protection built in — only suitable for older rewires where individual RCBOs are used on every circuit. Rare in new installations.
The most common domestic type before 2019. A 100A main switch feeds two RCD-protected busways, each covering half the circuits. The split-load design means a nuisance RCD trip only isolates half the installation, preserving lighting or sockets while the fault is traced.
Each circuit has its own RCBO (combined MCB + RCD). The main switch feeds a single busway; each RCBO provides individual overcurrent and RCD protection. Under Amendment 2 (2022), this configuration (or equivalent) is required for new installations because it prevents a single RCD fault from taking out multiple circuits.
Amendment 2 recommends (and in some circumstances requires) Arc Fault Detection Devices on circuits supplying bedrooms and sleeping accommodation. AFDD-equipped consumer units have AFDD combination devices (AFDD + RCBO) or separate AFDD modules in series with MCBs. See the Surge Protection Devices and AFDDs guide (article #96) for more detail.
The 2022 amendment to the 18th Edition introduced significant changes for consumer units:
All socket outlet circuits rated up to 32A must have 30mA RCD protection, regardless of installation method. All circuits in bathrooms and kitchens require RCD protection. Circuits supplying luminaires in dwellings are recommended to have RCD protection.
Regulation 531.3.6: Where more than one RCD is used, the circuits must be split so that no single device protects all circuits simultaneously. A single 100A main switch board with one RCD covering all circuits does not comply. The solution is either a split-load dual-RCD board (at minimum) or individual RCBOs per circuit.
The preferred method under the 18th Edition (and aligned with the consumer protection intent) is one RCBO per circuit. This:
Regulation 443: SPDs are now required in most dwellings where the consequence of a transient overvoltage would be intolerable (i.e., virtually all domestic premises with electronic equipment). Type 2 SPDs (plug-in or DIN-rail mounted) should be installed at the consumer unit. See article #96 for SPD types and selection.
Since 2016 (Part P amendment), consumer units in domestic premises must have a non-combustible enclosure (typically metal-clad, 1mm steel). Plastic consumer units are permitted only where the complete enclosure is non-combustible or where it is installed in a location inaccessible to ordinary persons (e.g., commercial premises, locked enclosures).
Consumer units must meet minimum IP2XC (BS EN 61439-3) to prevent accidental contact with live parts. Most compliant consumer units are IP40 or better.
Miniature Circuit Breakers (MCBs) protect circuits against overload and short-circuit current. They are characterised by:
Matched to the cable current-carrying capacity (CCC) and the expected load. Common ratings:
The tripping characteristic determines the short-circuit current at which the MCB trips instantaneously:
Type B is standard for domestic circuits. Type C is used for circuits with motors (heat pumps, pumps, extraction fans with high inrush current). Mismatching type (e.g., using Type D on a domestic socket circuit) may prevent the MCB from tripping fast enough on fault, creating a safety hazard.
MCBs are rated by their ability to interrupt fault current without damage. For domestic premises:
Calculate the Prospective Fault Current (PFC) at the consumer unit using Ze (external earth loop impedance from DNO) plus the impedance of the supply tails. If PFC exceeds 6kA, use 10kA devices or a limiting fuse upstream.
For domestic installations: Type A is the standard minimum. Always use Type A or better when supplying circuits with switch-mode power supplies, EV chargers, inverters, or similar.
An RCBO (Residual Current Breaker with Overcurrent protection) combines a Type B or C MCB and an RCD in a single 18mm DIN-rail device. Advantages:
The width (typically 18–24mm) means an RCBO takes more DIN rail space than an MCB. A 16-way MCB board needs to become a 24-way RCBO board if full RCBO coverage is required. Plan enclosure size accordingly.
Planning a consumer unit for a 3-bedroom semi-detached house with standard circuits. All circuits to use 30mA Type A RCBOs:
| Circuit | RCBO Rating | Cable | Notes |
|---|---|---|---|
| Downstairs lighting | B6A | 1.0mm² T&E | |
| Upstairs lighting | B6A | 1.0mm² T&E | |
| Ring final — ground floor sockets | B32A | 2.5mm² T&E | |
| Ring final — first floor sockets | B32A | 2.5mm² T&E | |
| Cooker circuit | B40A | 6mm² T&E | Cooker switch + connection unit |
| Electric shower 9.5kW | B40A or B45A | 10mm² T&E | Dedicated circuit |
| Immersion heater | B16A | 2.5mm² T&E | Time-switched |
| Dishwasher | B20A | 2.5mm² T&E | Unswitched spur |
| Washing machine | B20A | 2.5mm² T&E | Unswitched spur |
| Fridge/freezer | B20A | 2.5mm² T&E | Dedicated — never trips fridge |
| Garage/outbuilding | B32A | 6mm² SWA or 4mm² T&E | RCD protects against earth spikes |
| Spare ways (×3) | — | — | Future EV charger, solar, etc. |
Total: 11 circuits + 3 spares = 14-way minimum. Use a 16-way or 18-way consumer unit to allow for future growth. Add Type 2 SPD module in one way.
The main switch must be rated for the maximum demand of the installation. For domestic premises, the DNO typically provides a 100A service fuse at the meter. The consumer unit main switch should be 100A double-pole.
For larger installations (heat pump + EV charger + electric shower + cooker): check that diversity does not result in the 100A fuse being exceeded during simultaneous operation. If it does, upgrade the service fuse with the DNO, or use load management (demand side management) to prevent overload.
The meter tails between the DNO meter and the main switch must be:
Before connecting supply, complete the following tests (refer to Electrical Installation Testing guide, article #122):
After energisation:
Consumer unit installation or replacement is Notifiable Work under Part P of the Building Regulations (England and Wales). This means:
On completion, issue the customer:
See also: Building Regulations Part P guide (article #162) and Electrical Installation Testing (article #122).
APM stocks a range of consumer units, MCBs, and RCBOs suitable for domestic split-load board installations:
12-way metal consumer unit with 100A DP main isolator. Amendment 3 compliant metal enclosure. Suitable for domestic and light commercial split-load board replacement. 12 ways allows a full RCBO-per-circuit approach or accommodates dual-RCD configuration with 6+6 distribution. Comes without RCDs/MCBs for flexibility.
MK Sentry 12-way all-metal consumer unit. Amendment 3 compliant with 100A main switch/disconnect. Metal enclosure required under 18th Edition for consumer units in domestic premises. Accepts standard MK Sentry MCBs and RCBOs. Includes blanking plates.
Single-pole single-module RCBO providing overcurrent (20A) and residual current (30mA) protection. Type A rating detects pulsating DC fault currents from modern electronic equipment. Compact 1-module design maximises available ways in the consumer unit. Suitable for ring main and lighting circuit protection under BS 7671.
Type B single-pole MCB rated 6A for lighting circuits. Trip characteristic B suitable for resistive loads and standard lighting (no high inrush currents). BS EN 60898 rated. Fits MK Sentry consumer units. Common specification for new and replacement lighting circuit protection in domestic BS 7671:2018 installations.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment