Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Emergency escape lighting helps people leave safely when normal lighting fails. The fire-risk assessment, building layout and intended use determine the system required. Choose fittings against that design; a product’s wattage, duration or IP badge alone is not a compliance certificate.
Two existing APM product routes: V-TAC emergency exit-sign listing and Knightsbridge EMLED3 emergency-bulkhead listing. Confirm the exact supplied revision, operating mode, emergency performance, legends and contents before ordering. Recorded stock does not certify physical or allocatable availability.
Send a model or materials enquiry. Call 020 8702 8080 or WhatsApp our landline or 07737 263641 with safely accessible fitting-label photos, the design schedule and required quantities. Do not open equipment for photos. An enquiry is not a substitute for a fire-risk assessment or emergency-lighting design.
BSI lists BS 5266-1:2025 as the current code of practice, published on 29 October 2025. The previous 2016 edition should not be described as the current release. The designer should establish the standards and requirements applicable to the work, including the premises’ fire strategy and any existing-system assessment.
Government guidance for offices and shops explains that the premises and risks determine the emergency-lighting provision. Do not apply one blanket rule to every UK building: legislation and guidance differ by country and premises type. Identify escape routes, occupants’ needs and other safety functions before selecting a system.
A non-maintained emergency light normally illuminates on failure of the relevant normal lighting supply. A maintained fitting can provide normal lighting as well as emergency illumination. Some products permit switched maintained operation; “maintained” does not by itself mean every fitting must emit light continuously around the clock. Sign illumination while the premises are occupied and each fitting’s permitted configuration require separate checks.
Self-contained equipment has its emergency battery at or next to the fitting. A centrally supplied system has a different supply arrangement. Do not substitute an ordinary mains luminaire into a central system simply because its voltage appears suitable. Confirm the specified equipment and the complete system design.
Have the designer specify the required duration and emergency photometric performance. There is no safe purchasing shortcut of “one hour for offices, three hours for sleeping buildings”. A three-hour product rating does not prove that its light distribution, sign visibility or coverage meets the premises’ requirements.
Use the actual emergency-mode output and photometric data, mounting height and layout. Normal-mode lumens are not a substitute. Avoid generic spacing rules, fixed corridor centres or a room-area threshold used without the complete design conditions. Exit signs and escape-route illumination perform different tasks; a visible sign is not evidence that the route is adequately lit.
The design must account for a relevant local normal-lighting failure, not just a whole-building power cut. Eaton’s manufacturer design guide explains the importance of the local lighting supply in self-contained systems. A blanket instruction to place every emergency fitting on a separate final circuit can miss that requirement.
Have the competent designer and installer determine the supply, monitoring, control, circuit integrity and testing arrangements for the actual system. Do not copy generic terminal, cable-size or distribution-board recipes, and do not change a supply to resolve a shopping-guide example.
Arrange and record routine checks, functional testing and duration testing for the actual system. The government offices-and-shops guide describes daily checks of central controls, monthly functional tests and annual full-discharge testing. This is not a blanket instruction to cut a building’s supply or a fixed test-time recipe for every fitting.
Plan tests and the recharge period so occupants retain adequate protection. Keep results, defects and remedial actions in the system records; a lamp lighting briefly or a charging indicator alone does not establish the required duration and coverage. Ask the responsible person or competent maintenance provider how a fault affects continued use of the premises.
Self-test or addressable equipment still needs results reviewed and faults acted on. The DALI Alliance describes automated function and duration testing for suitable emergency control gear; that does not make an ordinary DALI driver an emergency unit or remove maintenance responsibilities.
Prepare the design schedule, exact existing labels, operating mode, required emergency performance, mounting and environment, legends and quantities. Confirm the actual item and delivery or collection options. Browse the APM emergency-lighting range as product options, not as an approved system package.
BSI current BS 5266-1 record; government offices-and-shops fire guidance; NVC operating-mode explanation; Eaton design guide; DALI emergency explanation; V-TAC exact EAN page; and Knightsbridge EMLED3L page for revision comparison only. Use the actual equipment instructions and competent system assessment; this buyer checklist is not an installation design or compliance certificate.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment