Free delivery from £50 on eligible UK orders
Free delivery from £50 on eligible UK orders · Collect from Acton · Trade & retail welcome
Mechanical Ventilation with Heat Recovery (MVHR) extracts stale, moisture-laden air from wet rooms and kitchens while simultaneously supplying fresh filtered air to living spaces. A heat exchanger core transfers typically 85–95% of the thermal energy from the outgoing air to the incoming stream, dramatically reducing the ventilation heat loss that accounts for 20–40% of a well-insulated home's total energy demand.
Since the 2022 amendments to Approved Document F, MVHR has moved from a niche specification into mainstream residential and commercial new-build work. Part F 2022 raised minimum whole-dwelling ventilation rates and tightened testing requirements, making MVHR the most straightforward route to compliance in airtight dwellings where background ventilators cannot provide sufficient air changes without unacceptable draughts.
MVHR is most cost-effective in dwellings with an air permeability below approximately 5 m³/(h·m²) at 50 Pa. In very airtight properties (≤3 m³/(h·m²)), natural and intermittent mechanical extract ventilation strategies struggle to meet Part F minimum rates without causing discomfort, making whole-dwelling MVHR the default choice.
Key indicators that MVHR should be specified:
The central unit contains two counter-flow or cross-flow air streams separated by a heat exchanger core. Better units use enthalpy (hygroscopic) cores that also transfer moisture, reducing internal humidity swings. Key specifications to check:
Semi-rigid insulated duct (typically 75 mm or 90 mm spigots expanding to 125 mm or 160 mm main runs) is the preferred system for residential work. Rigid galvanised or PVC circular duct suits commercial applications. Key rules:
Detailed duct sizing guidance is in our separate guide to Ventilation Ducting.
Circular or square extract valves are fitted in kitchen (above hob area), bathroom, en-suite, utility room, and WC ceilings. For bathrooms and shower rooms, fit humidity-sensitive valves that automatically boost extract rate when relative humidity exceeds 70–75%. See our guide to Bathroom Extractor Fans for valve types.
Supply diffusers in bedrooms and living spaces should be adjustable, low-velocity, and positioned to avoid draughts on occupants. Ceiling-mounted diffusers with 360° throw pattern are preferred; avoid pointing supply jets directly at seating areas.
Both fresh air intake and exhaust discharge penetrate the external envelope. Separation of at least 1 metre (ideally 2 metres) between intake and exhaust is required to prevent short-circuit recirculation. Fit bird-proof grilles with insect mesh. On extract terminals, a weather cap with backflow preventer stops wind-driven reverse flow.
Approved Document F Volume 1 (dwellings) sets whole-dwelling ventilation rates as a minimum. For a four-bedroom detached house, the design flow rate is calculated from:
Part F also mandates commissioning to SAP Q airflow testing protocol with results submitted to Building Control. From 2022, commissioning certificates from an appropriately qualified person (CIBSE Commissioning Code A or equivalent) are required for all new-build MVHR installations.
MVHR units are low-wattage appliances (typically 50–200 W) but must be on a switched, fused spur or dedicated circuit:
For wiring and cable selection, refer to our UK Electrical Cable Types guide and our guide to consumer unit MCB/RCBO selection.
The unit should be inside the thermal and airtightness envelope to prevent frost damage to the heat exchanger and duct condensation on supply runs. Insulated loft plant rooms, utility cupboards, and airing cupboards are common locations. Avoid uninsulated cold lofts unless the unit has frost protection rated to −15°C.
Heat exchangers produce condensate from the warm extract stream, especially in winter. Every MVHR unit requires a 22 mm or 32 mm condensate drain, trapped and connected to the foul drainage system or run to an external gully. A dry trap risks drain gas entering the unit.
MVHR only performs as designed in a reasonably airtight building. All duct penetrations through external walls or the airtight membrane must be sealed with airtight tape, foam, or proprietary collars. Sealing failure allows cold air infiltration that defeats the purpose of heat recovery.
Filters require inspection every 3–6 months and replacement typically annually. Ensure the unit is accessible: minimum 600 mm clear in front of the filter access panel. Communicate maintenance requirements to the end user or building manager at handover.
Post-installation commissioning must include:
| Fault | Likely Cause | Remedy |
|---|---|---|
| High condensation in rooms | Boost mode not activating, humidity sensors failed | Check sensor wiring; replace humidity valve |
| Frost damage to heat exchanger | Unit in unheated loft below −5°C | Insulate duct and unit, or fit frost protection heater |
| High noise | Duct velocity too high, resonating semi-rigid duct | Re-balance to reduce velocity; add flexible connection at unit |
| Reduced airflow over time | Filter blocked | Check and replace G4/F7 filters |
| Short-circuit odour | Intake too close to exhaust | Extend separation; reposition terminals |
MVHR is now standard practice on airtight new-build and deep retrofit projects. Specify units with SFP ≤0.45 W/(l/s), heat recovery efficiency ≥85%, and F7 supply filters. Size ductwork for 2–3 m/s velocity, keep runs inside the thermal envelope, and provide condensate drainage from day one. Commission to Part F 2022 SAP Q protocol and hand over maintenance documentation to the client. A correctly designed and commissioned MVHR system delivers comfortable, low-energy ventilation for the life of the building with minimal running cost.
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}
Leave a comment